Amprobe AT-6030 Advanced Wire Tracer Kit

Product By Flir Logo
Amprobe’s newest wire tracer combines a Receiver and powerful Transmitter to locate energized and de-energized wires, breakers, and fuses without having to disconnect any equipment. The Receiver features four tracing modes optimized for a range of applications. Its fully automatic breaker tracing capability saves time and eliminates the confusion of multiple false positives by detecting the highest recorded signal in a breaker or fuse. The Transmitter utilizes two optimized frequencies that allows for a clean and reliable signal. The Signal Clamp can be used in applications where there is no access to bare conductors by enabling the Transmitter to induce a signal into a wire through insulation. Whether you’re a novice user or an expert, the AT-6000 Amprobe Advanced Wire Tracer kit will help you get the job done fast.

AT-6000-R Receiver

AT-6000-T Transmitter

CT-400 Signal Clamp
Measurement CategoryCAT III 600 VCAT III 600 VCAT IV 600 V, CAT III 1000 V
Operating voltage0 to 600 V AC/DC0 to 600 V AC/DC0 to 1000 V AC
Operating frequencyEnergized: 6.25 kHz
De-Energized: 32.768 kHz
Energized: 6.25 kHz
De-Energized: 32.768 kHz
Wire tracing: 32.768 kHz
AC current measurement: 45 Hz to 400 Hz
Hazardous voltage detectionSee NCV detection> 30 V AC/DCN/A
Signal indicationsNumeric, bar graph display and audible beepLEDs and audible beepN/A
Response timeTip Sensor (energized/de-energized): 500 MS
NCV: 500 MS
Battery voltage monitoring: 5 sec
Line voltage monitoring: 1 sec
Battery voltage monitoring: 5 sec
Instantaneous
Current output of signal (typical)N/AEnergized circuit:
HI mode: 60 mA RMS
LO mode: 30 mA RMS
De-energized circuit:
HI mode: 130 mA RMS
LO mode: 40 mA RMS
Loop mode: 160 mA RMS
1 mA/A for AC current measurement with multimeter
Signal voltage output (nominal)N/ADe-energized circuit:
LOW: 29 V RMS, 120 Vp-p
HIGH: 33V RMS, 140 Vp-p
With CT-400:
loop model: 31 V RMS, 120 Vp-p
De-energized circuit:
2.4 V RMS, 24 Vp-p
Range detection (open air)Tip sensor (Energized):
Max distance via air: up to 20 ft (6.1 m)
Pinpointing: approx. 1.97 in (5 cm)
Tip sensor (De-energized):
Max distance via air: up to 14.7 ft (4.5 m)
Pinpointing: approx. 1.97 in (5 cm)
NCV detection (40 to 400 Hz):
Max. sensitivity: 90 V up to 6.56 ft (2 m)
Min. sensitivity: 600 V up to 0.39 in (1 cm)
N/AN/A
Kit ContainsAT-6020 kitAT-6030 kit
AT-6000-R Receiver
AT-6000-T Transmitter
TL-6000 Test Lead and Accessory Kit
CC-6000 Hard Carrying Case
User Manual
1.5 V AA (IEC R6) Batteries (12) (not installed)
Rechargeable Batteries (12) (not installed)
Battery Chargers (3)
CT-400 Signal Clamp